1001
WALL MOUNTED, ROOM SEALED,
FAN ASSISTED, GAS COMBINATION BOILER
Lichfield Road, Branston Industrial Estate, Burton Upon Trent, Staffordshire DE14 3HD
Tel. 08707 282 885 - Fax 08707 282 886
ALL SPECIFICATIONS SUBJECT TO CHANGE
Phone numbers:
Installer
Service Engineer
Serial No.
Read these Instructions thoroughly
before using the appliance
FERROLI HELPLINE
FOR SERVICE INFORMATION OR
HELP TELEPHONE: 08707 282 885
ALWAYS QUOTE YOUR SERIAL NUMBER
FOR IMMEDIATE ASSISTANCE
INSTALLATION
INSTRUCTIONS
Appr. Nr. B94.01A CE 0063AQ2150
01/01
G.C. NO: 47-267-19
Vue de la page 0
1 2 3 4 5 6 ... 31 32

Résumé du contenu

Page 1 - INSTRUCTIONS

1001WALL MOUNTED, ROOM SEALED,FAN ASSISTED, GAS COMBINATION BOILERLichfield Road, Branston Industrial Estate, Burton Upon Trent, Staffordshire DE14

Page 2

100110Flue systemThe boiler allows the flue outlet to be taken from the rear of the boiler or from either side.A standard flue length of 0.75 metres

Page 3 - Related Documents

100111Fig. 7NOTE: A bypass must be fitted as far as possible from the boiler if thermostatic radiator valves are fitted throughout.Fig. 6Key1. Filli

Page 4 - Technical data

100112Built-in Central Heating Water Circulating PumpThe pump head available for circulating the water is given in fig. 8.N.B. - The pump is factory

Page 5 - Appliance Dimensions

100113InstallationNote - To mount the boiler on the wall, a two person lift will be needed.1.0 UNPACKINGThe appliance is delivered in 2 cartons.1.1

Page 6 - Boiler Flow Diagram

100114Important Note - Always use two spanners to prevent twisting of soft copper pipework on the boiler.Flush out the water system.Note - The ma

Page 7

1001154.0 PREPARING THE FLUE ASSEMBLY4.1Rear Flue Outlet (fig. 12)Important - The aluminium flue pipe must protrude into the outside grill by 60

Page 8 - Installation Details

100116Fig. 14TOP VIEW BOILER SIDE OUTLET5.0 CONNECTING THE BOILER5.1 Place the boiler on its back.5.2 Remove the boiler base plate, four screws (fig

Page 9 - Minimum Clearance

100117Fixing pointsLift hereFig. 15Fixing screwsFig. 16 Fig. 17

Page 10

100118External controls: room stat or remote timeclock in the place of loop terminals 4 and 5.Please note 24 V only, use only voltage freecontacts.

Page 11

1001198.0 COMMISSIONING AND TESTING8.1 Filling the Central Heating SystemFig. 20Remove the top front panel by gripping both sides and lifting forwar

Page 12 - For syst. volumes other than

10012page INDEX3 General Description3 Related Documents4 Technical Data5 Appliance Dimensions6 Boiler Flow Diagram7 Key of boiler flow diagram8 Inst

Page 13 - Installation

1001208.5 To Light the Boiler (fig. 21)a. Open controls panel door.b. Switch on electricity supply.c. Adjust room thermostat and all external contro

Page 14 - Lower bracket

100121Burner Pressure C.H. and D.H.W.8.6 To Range Rate the Boiler C.H. (not required for standard installations).The boiler can be range rated for a

Page 15

100122Honeywell VR 4605 NA 4003 valvewith V7335A4014 ModuregGas pressure Adjustment1 - With the burner lit:2 - Connect suitable pressure gauge to bu

Page 16 - TOP VIEW BOILER SIDE OUTLET

100123Burner Perssure C.H.• Natural gas• L.P.G. (Propane)51015202530359 1011121314151617181920212223242526 27 28 299101112 13 14 15 16 17 18 19 20 2

Page 17 - Fig. 16 Fig. 17

1001248.7 D.H.W. Burner PressureThe domestic hot water burner pressure is not range rateable and not adjustable but the maximum andminimum burner pr

Page 18

1001251.1 Use buttons + and - to set 1st ON time eg. 6:00Display2.1 Use buttons + and - to set OFF time, eg. 9:00Display3.1 Use button + and - to se

Page 19 - 8.0 COMMISSIONING AND TESTING

100126AIR PRESSURE SWITCHFig. 46BLUEBLACKBLACK12BLACKDL 1EBROWNBLUE33112KROMSCHRODERHUBA 605213BROWNBLUE3BROWNKROMSCHRODERHUBA 6021223HUBA 605HUBA 6

Page 20

10012712345678LED631571718100100Spare Parts ListItem No. G.C. Part No. Makers Part No No. Off DESCRIPTION14 386816 800130 1 C.H. safety valve16 - 80

Page 21

100128Domestic Hot Water PerformanceFig. 1 - D.H.W. Pressure Drop VS. flowA=Standard with cold water Flow RestricterB=Cold Water Flow Restricter Rem

Page 22

10012916 Fan32 Central heating pump34 C.H. flow temperature sensor42 D.H.W. temperatuure sensor43 Air pressure switch46 Operator gas valve47 Modulat

Page 23 - • L.P.G. (Propane)

10013General DescriptionThe Ferroli 1001 is a wall mounted, room sealed, fan assisted, combination boiler for CentralHeating (C.H.) and domestic

Page 24

100130General Notes - For use on the 1001 fitted with VMF7 Printed Circuit Board*The central heating pump (32) will run to disperse heat if the t

Page 25 - Time Clock

100131Special Installation Possibilities: Two-pipe air intake/flue outletSpecial Air Intake/Flue OutletThe standard Flue/air intake hood on top of t

Page 26

Lichfield Road, Branston Industrial Estate, Burton Upon Trent, Staffordshire DE14 3HDTel. 08707 282 885 - Fax 08707 282 886ALL SPECIFICATIONS SUBJECT

Page 27 - Spare Parts List

10014Technical dataNATURAL GAS (G20) PROPANE LPG (G31)Nominal Heat Input D.H.W. & C.H. (gross) 34.8 kW 34.0 kWMinimum Heat Input D.H.W. & C.

Page 28

10015Appliance DimensionsFRONT VIEWLEFT SIDE VIEW REAR VIEWFig. 1Key1. Electricity cable entry2. Gas supply3. Domestic Hot Water outlet4. Domestic C

Page 29 - CONNECTOR X3

10016Boiler Flow DiagramFig. 2

Page 30 - ° signification:

10017Key1. Fixing point2. Flue terminal3. Flue/air intake hood4. Sealing gasket5. Room sealed compartment6. Control panel7. Gas inlet8. Domestic hot

Page 31

10018Installation DetailsGas Safety (Installation & Use) Regulations: 1994In the interest of safety, it is the law that all gas appliances are i

Page 32 - Service Engineer

10019Terminal PositionMinimum Clearance mmNOTES* Access to the front of the boiler must be available for maintenance (min. 600 mm).Fig. 5Fig. 3